2.1 SPRINKLER SPECIALTY PIPE FITTINGS - Flow Detection and Test Assemblies:
Product: Commercial Model M8000. Includes a flow switch, TESTanDRAIN Model 2500, Model 7600 3-way Globe Valve, and a M7500 Pressure Gauge.
** NOTE TO SPECIFIER ** Delete riser model not required.
- Riser Model: Pre-Assembled TESTanDRAIN Riser 1-1/4, 1-1/2. and 2 inches (32 mm, 38 mm, 51 mm):
- One-piece bronze casting, lettered on both sides allowing right or left side draining, horizontal or vertical installation.
- Inlet and Outlet (Cast bronze): ** NOTE TO SPECIFIER ** Delete inlet and outlet size not required.
- Inlet and Outlet: Threaded.
- Inlet and Outlet: Grooved 1-1/2 to 2 inches (38 mm to 51 mm).
- Inlet and Outlet: Threaded and Grooved 1-1/2 to 2 inches (38 mm to 51 mm).
- Standard: UL's "Product iQ" listing, or "Approval Guide," published by FM Global, listing. NFPA 13.
- Pressure Rating: 300 psig (2070 kPa).
- Size: Same as connected piping.
- Riser Model: Pre-Assembled TESTanDRAIN Riser 2-1/2, 3, 4, 6, and 8 inch:
- Schedule 10 fabricated steel body with 3mil powder-coated red finish.
- Inlet and Outlet (Schedule 40 steel).
- Inlet and Outlet: Grooved 2-1/2, 3, 4, 6, and 8 inches (64 mm, 76 mm, 102 mm, 152 mm) Models.
- Standard: UL's "Product iQ" listing, or "Approval Guide," published by FM Global, listing. NFPA 13.
- Pressure Rating: 300 psig (2070 kPa).
- Size: Same as connected piping.
- Valve Model 2500 TESTanDRAIN valve 1-1/4, 1-1/2, and 2 inch Models:** NOTE TO SPECIFIER ** Delete valve model not required.
- 1 inch (25 mm) FNPT. ** NOTE TO SPECIFIER ** Delete orifice size not required.
- Test Orifice Size: Nominal 2.8K (3/8 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 4.2K (7/16 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 5.6K (1/2 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 8.0K (17/32 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 11.2K (5/8 inch, ELO), as required by NFPA 13, latest edition.
- Valve Model 2500 TESTanDRAIN valve 2-1/2 and 3 inches Models:
- 1 inch (25 mm) FNPT. ** NOTE TO SPECIFIER ** Delete orifice size not required.
- Test Orifice Size: Nominal 2.8K (3/8 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 4.2K (7/16 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 5.6K (1/2 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 8.0K (17/32 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 11.2K (5/8 inch, ELO), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 14.0K (3/4 inch, ESFR), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal K25.2, as required by NFPA 13, latest edition.
- Valve Model 2500 TESTanDRAIN valve 4, 6, and 8 inches Models:
- 2 inches (51 mm) Grooved. ** NOTE TO SPECIFIER ** Delete orifice size not required.
- Test Orifice Size: Nominal 2.8K (3/8 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 4.2K (7/16 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 5.6K (1/2 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 8.0K (17/32 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 11.2K (5/8 inch, ELO), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 14.0K (3/4 inch, ESFR), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal K25.2, as required by NFPA 13, latest edition.
- Water flow alarm switch.
- Pressure Gauge: AGF Model 7500.
- 1/4 inch (6 mm), 3-way globe valve: AGF Model 7600.