132 series with threaded and press connections.
Balancing valve with flow meter. NPTFemale by Female threaded and integral press connections. Brass body.
Brass ball. Brass ball control stem, chromeplated. PTFE ball seal seat. PSU control stem guide. Brass flow meter body.Brass flow meter
bypass valve stem, chrome plated. Stainless steelflow meter springs. PSU flow meter float and indicator cover. Peroxide curedEPDM
seals. With preformed shell insulation inexpanded closed cell PE X.
Provide with optional inlet and outlet low leadbrass full port ball valves, NPT female by NPT female, for isolation,separately sourced, Code NA108 series, with separately-sourced low lead closenipples.
Water and glycol solutions. Maximum percentage ofglycol 50 per cent. Maximum working pressure 150 psi (10 bar). Working temperaturerange 14 to 230 degrees F (minus 10 to 110 degrees C). Flow rate range unit ofmeasurement gallons per minute (gpm). Accuracy plus or minus 10 per cent. Control stem angle of rotation 90 degrees.