Model 8611 Commercial Corner RiserPACK
- 2.1 SPRINKLER SPECIALTY PIPE FITTINGS - Flow Detection and Test Assemblies:
- Product: Commercial Model M8611. Includes a flow switch, TESTanDRAIN Model 1011A, Model 7600 3-way Globe Valve, and a M7500 Pressure Gauge and a model M7000 Pressure Relief Valve.
- Riser Model: Pre-Assembled TESTanDRAIN Riser 2, 2-1/2, 3, 4, and 6 inches (51mm, 64 mm, 76 mm, 102 mm, 152 mm):
- Inlet and Outlet (Schedule 10 steel): Grooved 2, 2-1/2, 3, 4 and 6 inches (51mm, 64 mm, 76 mm, 102 mm, 152 mm) Models.
- Schedule 10 fabricated steel body with 3mil (.08 mm) powder coated red finish.
- Standard: UL's "Product iQ" listing, or "Approval Guide," published by FM Global, listing. NFPA 13.
- Pressure Rating: 300 psig (2070 kPa).
- Size: Same as connected piping.
** NOTE TO SPECIFIER ** Delete valve not required.
- Valve Model 1011 TESTanDRAIN valve for a 2 inch (51 mm) Model:
- 1 inch (25 mm) FNPT.
** NOTE TO SPECIFIER ** Delete orifice size not required.
- Test Orifice Size: Nominal 2.8K (3/8 inch) , as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 4.2K (7/16 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 5.6K (1/2 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 8.0K (17/32 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 11.2K (5/8 inch, ELO), as required by NFPA 13, latest edition
** NOTE TO SPECIFIER ** Delete orifice size not required.
- Test Orifice Size: Nominal 2.8K (3/8 inch) , as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 4.2K (7/16 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 5.6K (1/2 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 8.0K (17/32 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 11.2K (5/8 inch, ELO), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 14.0K (3/4 inch, ESFR), as required by NFPA 13, latest edition.
- Valve Model 1011 TESTanDRAIN valve for a 4 or 6 inch (102 mm, 152 mm) Models:
- 2 inch FNPT.
** NOTE TO SPECIFIER ** Delete orifice size not required.
- Test Orifice Size: Nominal 2.8K (3/8 inch) , as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 4.2K (7/16 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 5.6K (1/2 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 8.0K (17/32 inch), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 11.2K (5/8 inch, ELO), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 14.0K (3/4 inch, ESFR), as required by NFPA 13, latest edition.
- Test Orifice Size: Nominal 25.2K, as required by NFPA 13, latest edition.
- Water flow alarm switch.
- Pressure Gauge: AGF Model 7500.
- 1/4 inch, 3-way globe valve: AGF Model 7600
- Pressure Relief Valve and Drainage Piping: AGF Model 7000 or AGF Lockable Model 7000L
** NOTE TO SPECIFIER ** Delete pressure rating not required.
- Pressure Rating: Factory rated at 175 PSI.
- Pressure Rating: 200 PSI.
- Pressure Rating: 225 PSI.
- Pressure Rating: 300 PSI.
- Body Material: Bronze body and stainless steel spring.
- Components: Nylobraid flexible tube, Two 1/2 inch (13 mm) NPT by barbed 90 degree elbows, external identification plate and integral flushing handle to remove debris.
- 1/2 inch (13 mm) MIPT inlet, 1/2 inch (13 mm) FIPT outlet.
- Relief pressure shall be factory set to project specifications.
- Relief valve shall operate to the OPEN position between 90% and 105% of the set pressure.
- Relief valve shall reseat or CLOSE at a minimum of 80% of set pressure.